      Application of anti-seismic support and hanger
      source:Youma (Jiangsu) Support Hanger Technology Co., Ltd. | 作者:SystemMaster | Release time: 2022-06-09 13:54:39
      The number of various electromechanical circuits in the electromechanical system of modern buildings is very large, the specifications and models are very complex, and the use functions are also different. In the daily work of the electromechanical system, whether the electromechanical pipeline has sufficient strength to fix the pipeline on the structure is the key to the normal operation of the entire electromechanical system; Whether it can be guaranteed not to be damaged under the action of the earthquake, and whether some lifeline systems can be guaranteed to operate normally, are also important factors related to the protection of people's lives and property.

      The electromechanical seismic support system is a support system that is firmly connected to the pipelines, groove systems and equipment of the building structure that has been seismically designed, and takes seismic force as the main load. The settings of the two support systems are not repeated but complement each other. Huang Qiaojun, Institute of Architecture, National Cheng Kung University, simulated the sprinkler pipeline of a parking lot in Puli Town, Nantou County with the shaking table of the earthquake test bench and came to the conclusion that the displacement of each point of the pipeline with the seismic support system is reduced by 5% compared with that without the seismic support installed. ~10 times, effectively improving the seismic performance of the pipeline system.

      Application scope of anti-seismic support and hanger in building mechanical and electrical engineering

      (1) All pipes larger than DN65mm;
      (2) All smoke prevention and exhaust system pipes;
      (3) All circular air ducts with a diameter greater than 0.70m;
      (4) All rectangular air ducts with a cross-sectional area greater than 0.38㎡;
      (5) Wire bridges with a weight of 15kg/m and above;
      (6) All portal hangers.

      Seismic support and hanger classification and layout principles
      The anti-seismic support and hanger can fully protect the mechanical and electrical systems in the earthquake, and can be used to resist the damage of the seismic force from the horizontal and vertical directions. According to the different electromechanical systems to be protected, seismic supports and hangers can be divided into pipeline seismic systems, air duct seismic systems and electrical (including electrical conduits, trunking and bridges) seismic systems.

      Seismic support and hanger classification and layout principles 
      (1) The lateral spacing requirements for seismic reinforcement of pipelines are: pipelines with rigid materials such as grooved connection pipelines, welded steel pipes, brazed copper pipes. The maximum distance between horizontal hangers shall not exceed 12m; for pipelines of non-rigid materials such as HDPE, horizontal hangers The maximum distance should not exceed 6m.

      (2) The longitudinal spacing requirements for seismic reinforcement of pipelines are as follows: pipelines with rigid materials such as grooved connection pipelines, welded steel pipes, brazed copper pipes, etc., the vertical hanger spacing shall not exceed 24m; for pipelines made of non-rigid materials such as HDPE, the horizontal hanger spacing shall be The maximum shall not exceed 12m.

      Layout principle of duct seismic support system 
      (1) The maximum spacing of the lateral seismic hangers of ordinary rigid air ducts is 9m, and the maximum spacing of longitudinal seismic hangers of ordinary rigid air ducts is 18m.

      (2) For the lateral seismic hangers of fiberglass, plastic and other non-rigid material air ducts, the maximum spacing is 4.5m. The maximum longitudinal spacing is 9m.

      Layout principle of electrical seismic support system 
      (1) The maximum lateral seismic spacing of rigid electrical conduits, wire ducts and bridges shall not exceed 12m, and the maximum longitudinal seismic spacing shall not exceed 24m.

      (2) The maximum horizontal seismic spacing of non-rigid material electrical conduits, wire ducts and bridges shall not exceed 6m, and the maximum vertical spacing shall not exceed 12m.

      Calculation principle of seismic support system 
      The installation form and arrangement principle of the seismic support and hanger are determined according to the strict mechanical calculation results, and the calculation of the seismic force must meet the requirements of the code.